SANEC
🌊 Desalination Plant — SCADA/HMI
SWRO · SEAWATER INTAKE · MMF · RO · HPP · BRINE · ERD · 9 SYSTEMS
03:09:50
9/9
UNITS RUNNING
0
ACTIVE ALARMS
44.9%
RO RECOVERY
279.5 mg/L
PERMEATE TDS
2039.4 kW
HP PUMP POWER
95.4%
ENERGY RECOVERY
3215.6 m³
PRODUCT VOLUME
◈ Stage-by-Stage Sensor Readings
01
Seawater Intake
SWI
RUNNING
Intake Flow
1020.2 m³/h
Salinity
36.3 ppt
Seawater Temp
26.8 °C
SDI (Raw)
5.7 SDI
Pump 1 Freq
49.7 Hz
Pump 2 Freq
46.8 Hz
Screen Diff. Level
0.1 m
02
Pre-Treatment
PRE
RUNNING
Coagulant Dose
11.7 mg/L
Flocculant Dose
0.5 mg/L
Post-DAF Turb.
0.9 NTU
pH
7.8 pH
DAF Pressure
5.3 bar
TSS Out
4.1 mg/L
03
Multimedia Filters
MMF
RUNNING
Filtered Turb.
0.2 NTU
Head Loss
0.4 m
Filter Flow
752.8 m³/h
SDI (Post-MMF)
2.2 SDI
Backwash Status
0 ON
Filter Run Time
33.9 hrs
04
RO Membrane System
RO
RUNNING
Recovery Rate
44.9 %
Permeate TDS
279.5 mg/L
Feed TDS
35842.4 mg/L
Salt Rejection
99.3 %
ΔP Feed-Conc.
1.4 bar
Net Feed Press.
60.8 bar
05
High Pressure Pumps
HPP
RUNNING
Discharge Press.
55.4 bar
HP Flow
868.1 m³/h
Motor Power
2039.4 kW
Pump Speed
2821.9 rpm
Vibration
1.7 mm/s
Bearing Temp
50.2 °C
06
Chemical Dosing
CDS
RUNNING
Antiscalant Dose
4 mg/L
Acid (pH Adj.)
2.6 mg/L
Sodium Bisulfite
3.4 mg/L
Cl₂ Dose (Post-RO)
0.8 mg/L
Lime (Remineralize)
13.3 mg/L
Post-Dose pH
7.8 pH
07
Product Water Tanks
PWT
RUNNING
Tank 1 Level
6.3 m
Tank 2 Level
4.6 m
Total Volume
3215.6 m³
Product TDS
252.4 mg/L
Residual Cl₂
0.6 mg/L
pH
7.7 pH
08
Brine Disposal
BRN
RUNNING
Brine Flow
589.9 m³/h
Brine Salinity
69.1 ppt
Brine Temp
29.8 °C
Diluted Salinity
47 ppt
Outfall pH
7.2 pH
09
Energy Recovery Devices
ERD
RUNNING
Energy Recovery
95.4 %
ERD Flow
410.7 m³/h
Brine Press. In
59.6 bar
Boost Press. Out
53.9 bar
Power Saved
957 kW
Specific Energy
3.2 kWh/m³